Functional safety: SIL, PFD and common cause failures

Functional safety explained: SIL levels, PFD calculation for 1oo1 and 1oo2 architectures, the common cause beta factor with an example, and ISO 13849.

https://www.electronics-engineering.com/en/functional-safety-sil-pfd-common-cause-failures/

No ratings yet: be the first to rate this page.

A press, a robot, a chemical reactor can kill. Functional safety concerns the functions of the control system that protect people: the emergency stop, light curtains, safety switches on guards, the automatic interlocking actions of a process plant. Standards require showing with numbers how reliable these functions are.

In this lesson you will learn: how to go from risk to a safety integrity level (SIL); how to calculate the average probability of failure on demand (PFD) for one channel and for two redundant channels, with the derivations; why common cause failures limit the benefit of redundancy, with a numerical example; and how the ISO 13849 standard applies to machines.

Risk and integrity levels

Risk combines the severity of a harm and its probability. The process is always the same: identify the hazards, estimate the risk, reduce it first with an inherently safe design (eliminating the hazard), then with guards, and only at the end with information (warnings, training). When the reduction is entrusted to a function of the control system, the standard IEC 61508 (and the standards derived from it, IEC 61511 for the process industry, IEC 62061 for machines) requires assigning it a safety integrity level (SIL), from 1 to 4.

Low-demand functions: the PFD

For functions that act rarely (low demand rate, at most once a year), the SIL is defined by the average probability of failure on demand (PFD):

SILAverage PFDRisk reduction
1from 10⁻² to 10⁻¹from 10 to 100
2from 10⁻³ to 10⁻²from 100 to 1000
3from 10⁻⁴ to 10⁻³from 1000 to 10 000
4from 10⁻⁵ to 10⁻⁴from 10 000 to 100 000

High-demand functions: the PFH

Functions that act often or continuously (typical of machines) are measured instead by the average frequency of dangerous failures per hour, PFH: from 10⁻⁶ to 10⁻⁵ /h for SIL 1, down to 10⁻⁹–10⁻⁸ /h for SIL 4. The number alone is not enough: the standard also requires constraints on the architecture (hardware fault tolerance, safe failure fraction) and measures against systematic failures, that is specification, design and software errors, which no probabilistic formula describes.

Undetected dangerous failures

A safety function stays idle for months; one of its failures can remain hidden until it is needed. What counts are the undetected dangerous failures, with rate \lambda_{DU}: those that would prevent the intervention and that automatic diagnostics do not discover. Only a complete periodic test, every T, finds them, after which the function is considered as new.

Sawtooth behaviour of the probability of failure on demand between two periodic tests
After each test the probability that the function is failed restarts from zero and grows roughly as lambda DU times t; at the next test it returns to zero. The average over an interval is about lambda DU times T divided by 2.

One channel: 1oo1 architecture

Theorem. For a single channel (1oo1 architecture) with \lambda_{DU}T \ll 1, the average probability of failure on demand is

    \[ PFD_{avg} \approx \frac{\lambda_{DU}T}{2} \]

Proof. With a constant failure rate, the probability that the channel is failed at time t after the test is 1 - e^{-\lambda_{DU}t} \approx \lambda_{DU}t (lesson on probability). A demand can arrive at any instant of the interval with equal probability, so we take the average:

    \[ PFD_{avg} = \frac{1}{T}\int_0^T\lambda_{DU}t\,dt = \frac{\lambda_{DU}T}{2} \]

∎

Two redundant channels: 1oo2 architecture

Theorem. For two independent channels, of which one is enough to intervene (1oo2 architecture),

    \[ PFD_{avg} \approx \frac{(\lambda_{DU}T)^2}{3} \]

Proof. The function fails only if both channels are failed; with independent failures the probability at time t is (\lambda_{DU}t)^2. The average over the interval is \frac{1}{T}\int_0^T\lambda_{DU}^2t^2dt = \lambda_{DU}^2T^2/3. ∎

The two formulas hold if the channels are tested together and if the test is perfect. The exact numerical calculation, with the exponential instead of the linear approximation, differs by less than 1 % for the values of the example that follows.

Common cause

Example: a lock-out pressure switch

Example. A lock-out pressure switch with \lambda_{DU} = 10^{-6}/h, tested once a year (T = 8760 h): PFD_{avg} = 8{,}76\cdot 10^{-3}/2 \approx 4{,}4\cdot 10^{-3}, SIL 2. Doubling it in 1oo2, the formula gives (8{,}76\cdot 10^{-3})^2/3 \approx 2{,}6\cdot 10^{-5}: it would seem SIL 4.

The beta factor

But the two pressure switches are identical, mounted on the same tap, calibrated by the same person: a calibration error, a clogging, an overvoltage can put them out of service together. The beta factor \beta is the fraction of failures that hits all the channels for a common cause, and that part behaves like a single channel: \beta\lambda_{DU}T/2 is added. With \beta = 5 %, the term is 0{,}05\cdot 4{,}4\cdot 10^{-3} = 2{,}2\cdot 10^{-4}, almost nine times the independent term: the total is about 2{,}4\cdot 10^{-4} and the function is SIL 3, not 4.

The common cause term dominates, so improving the rest does little. Testing the two pressure switches every six months (T = 4380 h) brings the total down to about 1.2·10⁻⁴: still SIL 3. The same happens by bringing \beta to 2 %: about 1.1·10⁻⁴. To reach SIL 4 one would have to act on several fronts together, and in practice SIL 4 is almost never required: if needed, the process is usually redesigned to remove the hazard.

How to fight it

  • Diversity: sensors of different physical principle or from different manufacturers;
  • physical separation: separate process taps, cables and power supplies;
  • staggered maintenance: calibrations done at different times, perhaps by different people;
  • more diagnostic coverage, which turns undetected failures into detected ones, which bring the plant to a safe state;
  • a shorter test interval, useful above all as long as the independent term dominates.

Machines and ISO 13849

For machines the standard ISO 13849-1 (2023 edition) is often used. It classifies the safety functions into performance levels (PL from a to e) on the basis of the category of the architecture (from B to 4: from the simple single channel to the two channels with diagnostics that detects every single fault), the mean time to dangerous failure of the components (MTTFD), the diagnostic coverage and the measures against common cause. The required level (PLr) is derived from the risk graph: severity of the injury, frequency of exposure, possibility of avoiding the hazard.

The PL also corresponds to a frequency of dangerous failures per hour: for example PL d between 10⁻⁷ and 10⁻⁶ /h, PL e between 10⁻⁸ and 10⁻⁷ /h, the same ranges as SIL 2 and SIL 3. For this reason a design made with ISO 13849 and one made with IEC 62061 can be compared.

Practical principles

  • the emergency stop is a complementary measure, it does not replace the guards; it has priority over everything and requires a manual reset;
  • safety contacts with positive opening: the contact opens mechanically even if it has welded;
  • safety circuits work on a resting current: a cut wire leads to the safe state, like the live zero of 4-20 mA (lesson on sensors);
  • certified safety PLCs are used, with dual processors and diagnostics, and safety input and output modules; the safety program is separate from the functional one and protected from changes.

In Europe the general requirements are set by the Machinery Directive 2006/42/EC, replaced by Regulation (EU) 2023/1230, applicable from 20 January 2027.

In summary

  • Functional safety requires quantifying the reliability of the protection functions: SIL 1–4 (IEC 61508, 61511, 62061) or PL a–e (ISO 13849).
  • For low-demand functions the average PFD matters: about \lambda_{DU}T/2 for one channel, (\lambda_{DU}T)^2/3 for two independent channels.
  • Common cause failures add \beta\lambda_{DU}T/2 and usually dominate: in the example they bring the redundant system from an apparent SIL 4 down to SIL 3.
  • Diversity, separation, diagnostics and periodic tests are the tools to reduce the PFD; the numbers must always be accompanied by architecture constraints and measures against systematic failures.